How Loud Is a Data Center?

Published measurements put the inside of a data hall at roughly 70 to 80 dBA, while the noise that reaches nearby homes has been measured at about 40 to 59 dBA.

Measure your room against 80 dB a data center

Press “Measure now” and allow the microphone to compare your surroundings with this level.

0
Threshold of hearing
30
Whisper
60
Conversation
85
Hearing risk (8 h)
120
Threshold of pain
140
Impulse limit
194
Max undistorted sound
A data center: 40–80 dB

Measured from nearby homes (40–59 dBA) to inside the server hall (70–80 dBA).

NIOSH recommended daily limit at 80 dBA: 25 h 24 min (85 dBA for 8 h, halved every 3 dB). Calculate a full day.

Two very different numbers

A data center is loud in one way for the people who work in it and in another way for the people who live near it, so the honest answer has two parts.

Inside the hall

Server fans and air handlers run all day at a steady pitch. A measurement study presented at the MIPRO conference in 2016 is widely cited for a range of 70–80 dBA in an average-sized facility. That is louder than a 70 dB vacuum cleaner and close to the point where you have to raise your voice. NIOSH notes that when you must raise your voice to talk to someone 3 feet away, the level is around 85 dBA, which is also its recommended limit for an 8-hour day. Whether staff need hearing protection depends on the measured level and how long they spend in the hall.

At the property line and beyond

Outside, the sound comes from rooftop chillers, cooling fans and, during tests or outages, backup generators. Virginia's legislative audit commission (JLARC) reviewed noise readings taken by county staff near data centers that had drawn complaints. The readings ranged from an estimated 40 to 59 dBA, typically below the 55 or 60 dBA residential limits in Loudoun, Prince William and Fairfax counties. JLARC notes these readings were total sound at complaint locations, not the isolated contribution of the data center.

Why a legal level still bothers people

JLARC's conclusion was that the problem is the character of the sound and not its volume. Residents describe a constant drone or hum, like a home air conditioner scaled up to an industrial size, that never stops at night. Much of that energy is low-frequency. Ordinances are written in A-weighted decibels, which discount low frequencies, so a meter can show a compliant number while the hum is clearly audible indoors. The report suggests localities consider a supplemental limit in C-weighted decibels and require sound modeling before construction near homes.

What changes the level

Measuring it yourself

To document a hum, log it over hours. Our noise monitor records level over time so you can compare night with day. Keep in mind that a phone microphone, like an A-weighted limit, under-reads low-frequency sound, so pair the numbers with notes on when the hum is audible. See the measurement guide for placement.

Sources

Frequently asked questions

How many decibels is a data center at the property line?

It varies with design and distance. In Northern Virginia, county readings at locations that prompted complaints ranged from an estimated 40 to 59 dBA, usually under the local 55 or 60 dBA residential limits.

Is data center noise harmful to hearing?

Not for neighbors. JLARC found the noise is not loud enough to damage nearby residents' hearing. Inside the halls, levels near 80 dBA or more are an occupational exposure question for staff.

Why can I hear a data center that meets the noise ordinance?

Ordinances use A-weighted decibels, which discount the low-frequency hum that data center cooling equipment produces, and the sound is constant, so it stands out at night.

Updated

Tools and guides