Smoke alarms: 85 dB at 10 feet
Residential smoke alarm manufacturers state horn loudness the same way: 85 dB at 10 feet (3 meters). First Alert and BRK literature describes this as meeting or exceeding the current UL standard for smoke alarms. Because the rating is given at 10 feet, the alarm is considerably louder if you are standing on a chair directly beneath it, and quieter in the next room.
| Where you are | Approximate level |
|---|---|
| 1 ft from the alarm (changing the battery) | about 105 dB |
| 10 ft, same room | 85 dB (rated) |
| 20 ft, open hallway | about 79 dB |
| Behind a closed bedroom door | substantially lower |
The 1 ft and 20 ft values are estimates from the 6 dB-per-doubling rule, not manufacturer data.
Building fire alarms: the NFPA 72 rule
For commercial and multi-family buildings, the National Fire Alarm and Signaling Code (NFPA 72) does not set one fixed loudness. It requires the signal to be clearly louder than whatever else is in the room. As summarized by fire departments and trade publications, audible appliances in public mode must be at least:
- 15 dB above the average ambient sound level, or
- 5 dB above the maximum sound level lasting at least 60 seconds, whichever is greater.
In sleeping areas there is a third condition: the level must be at least 75 dBA measured at pillow level, with any doors or partitions between the sounder and the bed in place. Recent editions also call for a low-frequency 520 Hz signal in sleeping rooms. Always check the edition your jurisdiction has adopted.
Why the door matters
What stands between you and the alarm matters as much as its rating. A closed door removes a good part of the sound, which is why alarms are installed inside bedrooms as well as in hallways, and why interconnected alarms that sound together are recommended.
Is the alarm itself harmful?
At 85 dBA, NIOSH's recommended limit is 8 hours, so an alarm heard from across a room during an evacuation is not a hearing concern. Right at the unit the level is higher, so keep tests short. More on the threshold at 85 dB.
Test what reaches your pillow
Press the test button on the hallway alarm, close the bedroom door, and read the level at the pillow with the decibel meter. Compare it with the 75 dBA benchmark and with your normal night-time background from the noise monitor. A phone is not a certified instrument, so treat a borderline reading as a reason to add an alarm in the bedroom, not as proof of compliance.
Sources
- BRK / First Alert: SM210L smoke alarm specification sheet
- San Francisco Fire Department: Sleeping Area Fire Alarm Requirements (NFPA 72 summary)
- Electrical Contractor Magazine: You Hear It First (NFPA 72 audibility)
- NIOSH: Noise and Occupational Hearing Loss
Frequently asked questions
How many decibels is a smoke alarm?
Household smoke alarms are rated at 85 dB measured 10 feet (3 m) from the unit.
How loud does a fire alarm have to be?
Under NFPA 72, at least 15 dB above average ambient sound or 5 dB above the maximum sound lasting 60 seconds, and at least 75 dBA at the pillow in sleeping areas.
Can a smoke alarm damage your hearing?
Not in normal use. At 85 dB the recommended daily limit is 8 hours. It is louder right at the unit, so limit time spent testing alarms at arm's length.